 | SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO STANDARD DC 24V/0.5A, 15 MM WIDTH, 5 PIECES PER PACKAGING UNIT |
Supply voltage |
Reverse voltage protection | Yes; when using the same load voltage as on the power module |
Load voltage L+ |
● Rated value (DC) | 24 V; From power module |
● Reverse polarity protection | Yes; polarity reversal can lead to the digital outputs being connected through |
Input current |
from load voltage L+ (without load), max. | 10 mA; Per channel |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, typ. | 0.8 W |
Address area |
Address space per module |
● with packing | 4 bit |
● without packing | 1 byte |
Digital outputs |
Number of digital outputs | 4 |
short-circuit protection | Yes |
● Response threshold, typ. | 1 to 1.5 A |
Limitation of inductive shutdown voltage to | (L+) -55 to -60 V |
Controlling a digital input | Yes |
Switching capacity of the outputs |
● Lamp load, max. | 5 W |
Load resistance range |
● lower limit | 48 Ω |
● upper limit | 3 400 Ω |
Output voltage |
● for signal "1", min. | L+ (-1 V) |
Output current |
● for signal "1" rated value | 0.5 A |
● for signal "1" permissible range for 0 to 60 °C, min. | 7 mA |
● for signal "1" permissible range for 0 to 60 °C, max. | 600 mA |
● for signal "0" residual current, max. | 0.3 mA |
Output delay with resistive load |
● "0" to "1", max. | 45 µs; Typical value |
● "1" to "0", max. | 90 µs; Typical value |
Parallel switching of 2 outputs |
● for increased power | No |
● for redundant control of a load | Yes; per module |
Switching frequency |
● with resistive load, max. | 800 Hz |
● with inductive load, max. | 2 Hz |
● on lamp load, max. | 10 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 60 °C, max. | 2 A |
Cable length |
● Cable length, shielded, max. | 1 000 m |
● Cable length unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions | No |
Diagnostics indication LED |
● Status indicator digital output (green) | Yes |
Parameter |
Remark | 1 byte |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels | No |
● between the channels and the backplane bus | Yes |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 13.10.2014 |