 | SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DI HIGH FEATURE 24V DC, 15 MM WIDTH WITH PARAM. F. INPUT DELAY DIAGNOSIS F. ENCODER SHORT- CIRCUIT W. LED SF (GROUP FAULT) 5 PIECES PER PACKAGING UNIT |
Supply voltage |
24 V DC | Yes; From power module |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
from backplane bus 3.3 V DC, max. | 10 mA |
from supply voltage L+, max. | Dependent on encoder |
Encoder supply |
Output voltage | min. L+ (-0.5 V), under load |
Short-circuit protection | Yes; Electronic |
Output current |
● Output current, rated value | 500 mA |
● Output current, permissible range | 0 to 500 mA |
Power loss |
Power loss, typ. | 0.4 W |
Address area |
Address space per module |
● with packing | 2 bit |
● without packing | 1 byte |
Digital inputs |
Number of digital inputs | 2 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input voltage |
● Type of input voltage | DC |
● Rated value, DC | 24 V |
● for signal "0" | -30 to +5 V |
Input current |
● for signal "1", typ. | 8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes; 0.1 / 0.5 / 3 / 15 ms |
— at "0" to "1", min. | 0.05 / 0.4 / 2.7 / 14.85 |
— at "0" to "1", max. | 0,15 / 0,6 / 3,3 / 15,15 |
— at "1" to "0", min. | 0.05 / 0.4 / 2.7 / 14.85 |
— at "1" to "0", max. | 0,15 / 0,6 / 3,3 / 15,15 |
Cable length |
● Cable length, shielded, max. | 1 000 m |
● Cable length unshielded, max. | 600 m |
Encoder |
Connectable encoders |
● 2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions | Yes |
● Short-circuit | Yes; Short-circuit of outputs to ground; module by module |
Diagnostics indication LED |
● Group error SF (red) | Yes |
● Status indicator digital input (green) | Yes; per channel |
Parameter |
Remark | 3 byte |
Diagnostics short-circuit | Disable / enable |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels | No |
● between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 35 g |
last modified: | 21.08.2014 |